Features: 68 kW, 85 KVA, 208/480 Volts, 3 Phase, Caterpillar 4 Cylinder Engine, Bottom Mounted Fuel Tank
Meter Reading: 8,083 Hours
Serial Number:
Location: Utah, United States
Zip/Postal Code:84104
(Salt Lake City-Ogden area)
Shipping: See shipping details for important pickup requirements and to get a shipping estimate
Inspection Report : Protected by IronClad Assurancenotes
Payment: Payment due within 3 business days after auction. See Details
Inspection Report Payment Shipping Financing  
Inspection Ratings Key
Limited use or recently replaced, free of visible wear or defects
Performs within the tolerances expected for age and type of item
Although performing, shows indication of needing repair or replacement
Needs immediate repair/replacement. Requires work if it is to perform
as expected
 
General Appearance
CE Mark (on or near data plate) No
Paint Scratches; chips; see photos for condition
Sheet Metal (fiberglass) Condition Minor dents; scrapes; surface rust in areas; see photos for condition
Cowling, Insulation and Belly Pans Damaged insulation
General Appearance #1
 
Control Station
Gauges Operational
Oil Pressure The fault indicator shuts off after the engine oil pressure rises.
Hour Meter Reading 8,083 Hours; Functional Hour Meter - IronPlanet makes no guarantees as to actual hours/miles; we can only report what can be visually observed.
Limited Function Check (cs) The main components are in place and operational.
Hour Meter Reading
 
Engine
Make and Model Caterpillar 4 Cylinder Engine
Fuel Type Diesel
Emission Control Label None found
Blow by @ idle (subjective observation) Minor
Starter Operational
Turbo or Blower Operational
Fuel System Operational
Exhaust System No visible damage
Radiator Missing overflow hose
Oil Leaks Fluid accumulation: side of engine; see photos
Fuel Leaks None seen
Cooling System Leaks None seen
Limited Function Check (Engine) The engine started and ran. See oil report.
Blow by @ idle (subjective observation)
 
Generator
The generator was not load checked during the inspection. IronPlanet does not guarantee the generators ability to run at its full rated kW output.
Generator Make and Model Generac 98A 01275 S Generator
Operating Voltage 208/480
Disconnect Switch Not operationally checked
Cables and Connections
Emergency Shut Off Switch Functional
Limited Function Check The generator could not be checked for electrical output.
Generator #1
Oil Sample Analysis Engine
date of analysis May 15, 2012
Silicon 9 PPM
Lead 0 PPM
Tin 0 PPM
Copper 4 PPM
Aluminum 2 PPM
Silver 0.1 PPM
Nickel 0.4 PPM
Chromium 0.1 PPM
Iron 5 PPM
Glycol NEG
Water NEG
Fuel <5%

Disputes: This item is offered with IronClad Assurance® protection. With IronClad Assurance®, if a buyer discovers that the item is not substantially in the condition as represented in this inspection report, the buyer may submit a written dispute claim to IronPlanet. Following submission of a written dispute claim, IronPlanet will investigate the claim, re-inspecting the equipment item as necessary, and determine a fair and mutually beneficial resolution. Please note that IronPlanet inspections are performed solely for the purpose of reporting the visible condition of the equipment''s major systems and attachments on the day of the inspection and do not include load testing or digging/lifting. These inspections are not designed nor intended to detect latent defects, or conditions that could only be found in connection with the physical dismantling of the equipment or the use of diagnostic tools or techniques. This inspection report includes ratings, comments, and photos of the various components of the item. Knowledgeable buyers are expected to carefully review all of the available information in the inspection report, including all photographs, in order to make the best bidding and buying decision possible.
Warranty by Premium 2000

Place holder (To be provided by P2000)

TO DO: Window size adjustments based on actual data

Engine Coverage.  some text.

Transmission Coverage.  blah blah.

Affordable plans.

Learn more!
Copyright © 1999-2013 IronPlanet, Inc. All Rights Reserved. IronPlanet®, TruckPlanet℠, IronClad Assurance® and Auctions you can trust® are service marks of IronPlanet, Inc. All other marks and brands are the property of their respective owners.